masthead-innerpage-bg

C175-20

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Take Virtual Tour

  • Rugged, durable design with reliable performance proven in thousands of applications worldwide
  • Certified alternative fuels including Hydrotreated Vegetable Oil (HVO), Renewable Diesel (RD) and Hydrotreated Renewable Diesel (HRD) which meet EN 15940 or ASTM D975 can be used or blended with EN 590 diesel

  • Accepts 100% block load in one step
  • Meets NFPA 110 loading requirements
  • Conforms to ISO 8528-5 G3 load acceptance requirements
  • Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing

  • Superior motor starting capability minimizes need for oversizing generator
  • Designed to match performance and output characteristics of Cat diesel engines

  • Cooling systems are available to operate in ambient temperatures up to 50°C (122°F)
  • Tested to ensure proper generator set cooling

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirements
  • Expansion modules and site specific programming for specific customer requirements
  • Graphical touchscreen display
  • Easily upgradeable

  • 24 months/1000-hour warranty for Standby and Mission Critical ratings
  • 12 months/unlimited hour warranty for Prime and Continuous ratings
  • 12 months/unlimited hour warranty for Prime-DCP ratings
  • Extended service protection is available to provide extended coverage options

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

  • Caterpillar offers an array of financial products to help you succeed through financial service excellence
  • Options include loans, finance lease, operating lease, working capital, and revolving line of credit
  • Contact your local Cat dealer for availability in your region
Standby Rating
4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Rating
3600 (no fan)/3500/3300 (no fan)/3180 ekW
Emissions/Fuel Strategy
Low Fuel, Tier 2
Voltage
480 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous
Maximum Rating
4000 ekW
Minimum Rating
3150 ekW
Engine Model
C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Bore
6.89in
Stroke
8.66in
Displacement
6456.31in³
Compression Ratio
15.3:1
Aspiration
Turbo Aftercooled
Fuel System
Common Rail
Governor Type
ADEM� A4
Length – Minimum
262.5in
Length – Maximum
331.1in
Width – Minimum
92in
Width – Maximum
128.5in
Height – Minimum
99.8in
Height – Maximum
150.7in
Dry Weight – Genset (minimum)
55100lb
Dry Weight – Genset (maximum)
66200lb

Take the virtual product tour

Explore the features and Benefits
of the C175-20

Compare products

See how C175-20 compares against frequently compared products

Compare our equipment

Translate »