- Independently certified to meet IEC 61439-2:2011 BS & international standard.
- Standard ACB breaker range 1600A – 4000A CE & EAC marked.
- Standard breaker fault rating 65 kA Icc, option for 100kA Icc ABB Emax 2 E4.
- Certified assembly high fault rating, tested up to 100 kA / 1s ICW
- Certified standard temperature rise tested.
- Design verification to Annex D of IEC 61439-2:2011
- Smaller footprint matched to the generator packaged design.
- Innovative cableway management.
- Modularity:
- Built around 150mm modules in 3 axis.
- Framework utilises a 25mm grid allowing a fully configurable system.
- Easy to extend and upgrade.
- Copper HDHC:
- Standard 10mm copper with 10mm spacing improves heat rejection.
- Stainless steel mounted busbar supports, reduce eddy currents.
- Fully tinned option.
- Breaker options:
- Accommodates fixed or withdrawable breakers.
- 3 or 4 pole option.
- Manual or motorized option.
- ACB door selection option.
- Enclosure options: o Options up to Form 4b separation.
- Configurable for top or bottom entry.
- Swivel lifting eye (4 point lift) for single sections.
- IP54 protection option.
- 50 °C option.
- Option to include generator controllers or PLC.
- EPD white powder coated, option for custom colours.
- In house automated routine testing.
- Rating plate.
- Cat warranty.