Design Criteria
Design Criteria The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.
Generator
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • EMCP Control Panel
    EMCP Control Panel The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further...
    World Wide Product Support
    World Wide Product Support Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted f...
    UL 2200 / CSA - Optional
    UL 2200 / CSA - Optional
  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.
  • Single-Source Supplier
    Single-Source Supplier Fully prototype tested with certified torsional vibration analysis available
    Design Criteria
    Design Criteria The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.
    Generator
    Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
  • EMCP Control Panel
    EMCP Control Panel The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
    World Wide Product Support
    World Wide Product Support Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
    UL 2200 / CSA - Optional
    UL 2200 / CSA - Optional
  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.
  • Single-Source Supplier
    Single-Source Supplier Fully prototype tested with certified torsional vibration analysis available

    Engine Specifications

    Bore
    5.4in
    Displacement
    1649.47in³
    Stroke
    6in
    Aspiration
    TA
    Fuel System
    MEUI
    Engine Model
    C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
    Compression Ratio
    16.0:1
    Governor Type
    Adem™A4
    Aspiration
    TA
    Fuel System
    MEUI
    Bore
    5.4in
    Displacement
    1649.47in³
    Stroke
    6in

    Generator Set Specifications

    Minimum Rating
    725 ekW
    Maximum Rating
    800 ekW
    Voltage
    208 to 600
    Frequency
    60 Hz
    Speed
    1800 RPM
    Emissions/Fuel Strategy
    EPA Tier 4 Interim

    Standard/Optional Features

    Standard Equipment:

    • Air Inlet
      • Single element canister type with service indicator
    • Control Panel
      • EMCP 4 / EMCP 4.2B genset controllers
      • EMCP 4.2B Control features
      • Communications
      • Programmable protective relaying functions
      • Warning/shutdown Indicators
      • Digital Indicators
    • Cooling
      • Fan and belt guards drive
      • Coolant level sensor
      • Caterpillar extended life coolant
      • Radiator sized to 50 degrees C
      • Coolant drain line with valve terminated on edge of base
      • ATAAC
    • Exhaust
      • Exhaust manifold - dry
      • 203 mm (8 in) ID round flanged outlet
    • Fuel
      • Primary fuel filter with water separator
      • Fuel cooler
      • Flexible fuel lines - installed
      • Electric fuel priming pump
      • Secondary fuel filters
    • Generator And Attachments
      • SR5 Permanent magnet excitation (PMG) (PM)
      • For Low BSFC configurations:
      • Integrated voltage regulator (IVR) includes
      • Busbar connections:
    • Lube System
      • Integral lube Oil cooler
      • Standard volume oil pan - 68 Ltr
      • Lubricating oil
      • Oil filter, filler and dipstick
      • Gear type lube oil pump
      • Oil drain lines and valve
      • Fumes disposal - open crankcase ventilation routed to front of package
    • Mounting System
      • Rails - engine/generator/radiator mounting
      • Rubber anti-vibration mounts - shipped loose
    • Starting And Charging System
      • 24-volt electric starting motor
      • Charging alternator 45A
      • Battery, rack and cables - shipped-loose
      • Battery disconnect switch
    • General
      • Flywheel and flywheel housing-SAE No. 0 and SAE No. 18
      • SAE standard rotation
      • RH service
      • Paint - Caterpillar yellow with high gloss black rails & radiator

    Optional Equipment:

    • Air Inlet System
      • Standard air cleaners
      • Dual element air cleaners
      • Heavy duty air cleaners
    • Battery / Charging System
      • 10 Amp Battery chargers
      • 20 Amp enclosure Battery chargers
      • 24 Volt battery set - Dry
      • 24 Volt electric start motors - Heavy duty
      • Jacket water heaters
      • Air starting motor with control and silencer
      • Space heater
    • Circuit Breakers
      • 400, 800, 1200, 1600, 2000, 2500, 3000 Amp, 3 pole, UL-100% rated Circuit breakers
      • 2000 Amp, 3 pole, IEC rated Circuit breakers
      • 800 Amp, 4 pole, IEC rated Circuit breakers
    • Control Panels
      • EMCP (4.2B) (4.3) (4.4)
      • Remote mounting harness
      • Remote mounted circuit breaker terminals
      • Remote mounted panel harness mounting kit
      • Auxiliary box options
      • Side extension box
      • Cable shroud - Top mounted
      • Cable shroud - Bottom mounted
      • Cat connect telematics
      • Installed DIO module
      • Remote DIO module
      • Annunciator modules
      • Remote annunciator module
      • Modbus monitor local packages
      • Load share module
      • Vandal proof panel cover
    • Cooling System
      • Standard radiator
      • High ambient radiator
      • Certified radiator
      • Extended life coolant
      • Radiator duct flange
    • Enclosures
      • Special Sound attenuated enclosure
      • Enclosure with lifting base or fuel tank
      • Enclosure fuel tank options
      • Enclosure louvers
      • Cold weather bundle
      • Enclosure lighting
      • AC distribution panel, lights and outlet
      • Panel bracket
      • Enclosure colors
    • Exhaust
      • Flanges
      • Guard and shield system
      • Elbows
      • Flexible fittings
      • Mufflers
      • Exhaust through the wall kit
    • Generator And Attachments
      • 60 Hz standard generators
      • 60 Hz premium generators
    • Lube System
      • Oil level regulator
      • Prelube pumps
    • Mounting System
      • Puck style low efficiency isolators
      • Spring type vibration isolators
      • IBC vibration isolators
      • Mounting base type
    • Power Connections
      • Neutral grounding connection
      • Center post busbars
      • Power connections - Right / Left / Rear
      • Cable entry - right/left/rear
    • Starting/charging
      • Battery chargers
      • Oversize batteries
      • Jacket water heater
      • Heavy duty starting system
      • Charging alternator
      • Air starting motor with control and silencer
    • Special Tests / Reports
      • IBC seismic Certifications
      • OSHPD seismic Certifications
      • Special CSA test Certification
      • PGS Test report @ 1.0 power factor
      • PGS Test report @ 0.8 power factor
      • Generator test report
      • Standard engine test
      • Torsional vibration analysis report
    • General
      • Special paint
      • US aid emblem
      • Miscellaneous inspection
      • EU Certificate of Conformance (CE)

    Take The Virtual Product Tour To Explore The Features And Benefits of the C27 Tier 4 Interim

    See how C27 (60 Hz) Tier 4 Interim compares against frequently compared products

    C27 (60 Hz) Tier 4 Interim Diesel Generator Sets

    Engine Model
    C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
    Voltage
    208 to 600
    Maximum Rating
    800 ekW
    Selected Model

    C1.5 (50 Hz) Diesel Generator Sets

    Engine Model
    Cat® C1.5
    Voltage
    110 to 415 Volts
    Maximum Rating
    13.5 kVA
    View Full Specs

    C1.1 (50 Hz) Diesel Generator Sets

    Engine Model
    C1.1, In-line 4 4-cycle diesel
    Voltage
    110 to 415 Volts
    Maximum Rating
    9.5 kVA
    View Full Specs