Open Generator Set

DG250-2 (Single-phase)

Electric Power
Electric Power (354)

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Displacement
864.71in³
Fuel Type
Natural Gas
Voltage
120 / 240 VAC
Emissions/Fuel Strategy
U.S. EPA Certified for Stationary Emergency Application
Frequency
60 Hz
Natural Gas Rating
175 eKW
Speed
1800 RPM

Engine Specifications

Bore
5.31in
Compression Ratio
9.5:7
Fuel System
Natural Gas
Stroke
6.5in

Standard/Optional Features

Standard Equipment:

  • Cooling
    • Closed coolant recovery system
    • Factory-installed radiator
    • 50/50 Ethylene glycol antifreeze
    • Standard ambient temperatures up to 50°C (122°F)
    • Radiator and cooling fan complete with protective guards
  • Air Inlet
    • Single element air filter
  • Fuel
    • Fuel pressure test po
    • Primary and secondary fuel shut-off
    • Low fuel pressure switch
    • Natural Gas or LP Vapor
    • Dual lock off valves
    • NPT connection
  • Exhaust
    • Exhaust outlet with 3” pipe
  • Generator
    • Full load capacity alternator
    • Class H insulation material
    • Permanent magnet excitation
    • Permanent magnet excitation
    • Full load capacity alternator
    • Class H insulation material
    • Integrated Voltage Regulator
    • Matched to the performance and output characteristics of Cat engines
    • IP23 Protection
  • Controls
    • EMCP 4.2 Series generator set controller
  • Mounting
    • Vibration isolaton (puck type)
    • Rubber vibration isolators
  • Electric Starting And/or Prelube
    • Solenoid activated starter motor
    • Engine electrical system
    • Battery cables
    • Solenoid activated starter motor
  • Electric Power - Package Serial Number Prefix
    • Battery charging alternator
  • Governor
    • Electronic governor (non adjustable)
  • Control Panel
    • EMCP 4.2 Series generator set controller
  • Starting/charging
    • Batteries with rack and cables
    • 12 volt starting motor

Optional Equipment:

  • Starting/charging
    • Battery heater
    • Battery charger – UL Listed 10 amp
    • Charging alternator
    • Jacket water heater
  • General
    • UL 2200 package
    • Suitable for Use as Service Equipment (SUSE)
    • Enclosures: sound attenuated, weather protective
    • Automatic transfer switches (ATS)
    • CSA Certification
  • Generator
    • Oversize and premium generators
    • Anti-condensation heater
    • Excitation: [ ] Permanent Magnet Excited (PM)
    • Shunt trip and auxiliary contact breaker
    • Thermal magnetic or electronic trip MCCBs
    • Anti-condensation heater

Take The Virtual Product Tour To Explore The Features And Benefits of the DG250-2 (Single-phase)

See how DG250 GC (Single-phase) compares against frequently compared products

DG250 GC (Single-phase) Electric Power

Selected Model

Electric Power

View Full Specs

Electric Power

View Full Specs

Compare with other Cat Models

Compare Now

Media Gallery

Check out our current offers

View Specials
Translate »