ATC Power Breaker & Case Switch Automatic Transfer Switch
ATS ATC Breaker / Contactor
ATS ATC Breaker / Contactor (8)
- ATC-800 CONTROLLER
- ATC Power Breaker Bypass Isolation Open/Closed Transition Automatic Transfer Switch
- ATC-300+ CONTROLLER
- ATC Contactor Based Bypass Isolation Automatic Transfer Switch
- ATC Molded Case Circuit Breaker & Molded Case Switch Automatic Transfer Switch
- ATC Service Entrance Rated MCCB & Power Breaker Based ATS
- ATC Contactor-Based Automatic Transfer Switch
- ATC Power Breaker & Case Switch Automatic Transfer Switch
Overview
Cat® transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a compact package. The open transition power case switch-based Automatic Transfer Switch (ATS) will provide fully functioning transfer in applications where a momentary loss of power is acceptable on retransfer from emergency to normal power supply. The Cat power case switch-based ATS also permits periodic testing of the emergency source without interrupting power to the loads and are available from 200 to 5000.
Product Features
- ATC-800 microprocessor-based controller
- Voltage and frequency sensing
- Fastest switching times available (<3 cycles)
- Full 60-cycle short time withstand capability
- Multiple field programmable time delays
- Switch position indication
- Source availability indication
Product Features
- ATC-800 microprocessor-based controller
- Voltage and frequency sensing
- Fastest switching times available (<3 cycles)
- Full 60-cycle short time withstand capability
- Multiple field programmable time delays
- Switch position indication
- Source availability indication
- Safe manual transfer under load
- Source 1 and 2 auxiliary contacts
- Programmable plant exerciser
- System test pushbutton
- Load shed from emergency
- Mimic diagram
- True RMS three phase voltage sensing on Source 1, Source 2 and Load
- Frequency sensing on Source 1 and Source 2
- Mechanical (cable) and electrical interlocking to prevent paralleling of sources
- Safe manual operation under full load with permanently affixed operating handle
- Ambient temperature range: -40°C to 40°C (-40°F to 104°F)
- Operating temperature range: -20°C to 70°C (-4°F to 158°F)
- Operating humidity: up to 90%
- Relative humidity (non-condensing)
- Source paralleling duration is limited to 100 msec or less
- Source availability indication
Technical Summary
- Rating Range
- 200 to 5000A
- Transfer Type
- Open Transition
- Switch Type
- Power Breaker
- Rating Range
- 200 to 5000A
- Transfer Type
- Open Transition
- Switch Type
- Power Breaker
Ratings
- Control Power
-
Fixed Mount 200-3200A 2, 3, or 4 Pole
Drawout 200-5000A 2-, 3-, 4-pole - System Voltage Application
- 120 - 600 Vac, 50/60 Hz
- Time Withstand
- 85,000 for 30 cycles
- Withstand
- 100,000 amps withstand/closing/ interrupting at 600 Vac
- Applicable Testing
-
CSA C22.2 No. 178 certified
IBC 2006, CBC 2007 and OSHPD
Standard/Optional Features
Standard Equipment:
-
- Controls And Wiring
-
- All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating.
-
- Enclosure
-
- Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
Optional Equipment:
-
- Available Options
-
- Load sequencing contacts
- Multi-meter options available
- Controller availability: ATC-100, ATC-300+,and ATC-800
- 2- or 4-position test switch
- Remote communications
- Integral overcurrent protection
- Field selectable, multi ratio, control voltage transformer 50/60 Hz
- Suitable for service entrance
- Space heaters
- Open or closed transition
- Surge suppression
- Selectable automatic or non-automatic operation
-
- Optional Delayed Transition Includes:
-
- Time delay neutral
- In-phase transition
- Pre-transfer signal with 1 N.O. and 1 N.C. contacts