3512 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Request a Quote
Bore
6.69 in
Displacement
3161.03 in3
Stroke
7.48 in
Aspiration
TA

Videos not available for this product.

Product Specs

Engine Specifications

Bore
6.69in
Displacement
3161.03in3
Stroke
7.48in
Aspiration
TA
Fuel System
Direct Unit Injection
Engine Model
3512 TA, V-12, 4-Stroke Water-Cooled Diesel
Compression Ratio
13.5:1
Governor Type
Woodward
Aspiration
TA
Fuel System
Direct Unit Injection
Bore
6.69in
Displacement
3161.03in³
Stroke
7.48in
Fuel System
7.48in

Generator Set Specifications

Minimum Rating
1000 kVA
Maximum Rating
1400 kVA
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Emissions/Fuel Strategy
Low Fuel Consumption
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Generator Set Dimensions

Height - Maximum
93.2in
Length - Maximum
206.6in
Width - Maximum
77.8in
Length - Minimum
202.7in
Dry Weight - Genset (minimum)
22650lb
Dry Weight - Genset (maximum)
23170lb

Standard/Optional Features

Standard Equipment:

  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
  • Control Panel
    • EMCP4.2 controls including: Emergency stop pushbutton
    • Failure to start (overcrank)
    • Accessory module data link
    • Over / under voltage (27 / 59)
    • EMCP4.2 controller including:
    • Engine cycle crank
    • Generator phase sequence
    • Generator mounted - rear facing
    • 2 programmable relay outputs (Form C)
    • Warning/shutdown with common LED indication of shutdowns for:
    • Alarm acknowledge
    • 24-volt DC operation
    • Overcurrent (50 / 51)
    • Reverse Reactive Power (kVAr) (32RV)
    • Communications:
    • Programmable protective relaying functions:
    • Environmental sealed front face
    • Low coolant level
    • Coolant temperature
    • 2 programmable digital outputs
    • Speed adjust
    • Emergency stop
    • Frequency (Hz)
    • 4 programmable relay outputs (Form A)
    • Volts (L-L & L-N)
    • High coolant temperature
    • kVA (per phase, average & percent)
    • Text alarm / event descriptions
    • Controls:
    • True RMS AC metering, 3-phase, +/-2% accuracy
    • Lamp test
    • Digital indication for:
    • Auto / start / stop control
    • kW-hr (total)
    • kVAr (per phase, average & percent)
    • Operating hours
    • Serial annunciator module data link
    • Reverse Power (kW) (32)
    • Oil pressure (psi, kPa or bar)
    • RPM
    • Amps (per phase & average)
    • Power Factor (per phase & average)
    • Engine cool-down timer
    • DC volts
    • Low coolant temperature
    • Over / under frequency (81 o / u)
    • kVAr-hr (total)
    • 6 programmable digital inputs
    • Customer data link (Modbus RTU)
    • Low oil pressure
    • kW (per phase, average & percent)
    • Overspeed
  • Cooling System
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Coolant drain line with valve
    • Fan and belt guards
    • JWAC
    • Coolant level sensors. (Not included with packages without radiator)
    • Radiator fan and fan drive
  • Exhaust System
    • Dry Exhaust Manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Flexible fuel lines - shipped loose
    • Fuel cooler; not included with packages without radiator
    • Fuel priming pump
    • Secondary fuel filters
  • Generators And Attachments
    • 3 Phase voltage sensing
    • Reactive droop capability
    • Exciter diode monitor
    • Generator set packages include: Regulator (CDVR)
    • 6 Lead
    • KVAR/PF modes
    • Note: 1800 frames are form wound, permanent magnet, with winding temp detectors
    • NEMA Class H insulation
    • Min / max exciter limiter
    • Busbar connections, top center mounted, top cable entry
    • Caterpillar's Digital Voltage Regulator (CDVR) includes:
    • LV:
    • Class H temperature rise at 40C ambient (125C prime/150C standby)
    • Random wound
    • Winding temperature detectors
    • 3 Phase brushless, salient pole
    • RFI suppression
    • Internal Excitation
    • 50 Hz models: IEC standard hole pattern
  • Governing System
    • Woodward 2301A isochronous governor
  • Lube System
    • Gear type lube oil pump
    • Oil drain lines and valve
    • Integral lube oil cooler
    • Lubricating oil
    • Oil filter, filler and dipstick
    • Fumes disposal
  • Mounting System
    • Rubber anti-vibration mounts (shipped loose)
    • Rails - engine/generator/radiator mounting
  • Starting / Charging System
    • 24 Volt electric starting motor
    • Battery disconnect switch
    • Battery and battery rack w/cables
  • General
    • Paint - Caterpillar Yellow with high gloss black rails & radiator
    • SAE Standard Rotation
    • RH Service
    • Flywheel and Flywheel housing - SAE No. 00

Optional Equipment:

  • Air Inlet System
    • Remote air inlet adaptors
    • Dual Element air cleaners
    • Air Inlet protection
  • Circuit Breakers
    • Controls packaging - Enclosures
    • Center posts busbars
    • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated circuit breakers
    • Optional busbar power connections
    • Busbar connections
    • Cable entry options
    • Breaker harnesses
    • EMAX circuit breakers
    • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated circuit breakers
    • EMAX breakers connections
  • Control Panel
    • Customer Interface Options
    • Annunciator Modules
    • Generator Temperature Monitoring
    • Customer connection mounting locations
    • Ground (Automatically selected)
    • EMCP 4.3, EMCP 4.4
    • Vandle proof panel door
    • Local PC monitoring
    • Auxiliary Boxes
    • Governors
    • Mounting Group - External Box Clips
    • Remote speed adjust
  • Cooling System
    • Heat exchangers
    • Water level switch gauges
    • Optional radiator arrangements
  • European Certifications
    • Eurasian conformity (EAC) mark
    • European directive genset, DoI (Declaration of Incorporation)
    • EU declaration of conformity
    • European Union Certification
  • Exhaust System
    • Flexible fittings
    • Mufflers
    • Muffler mounting kits
    • Through-wall installation kit
  • Fuel System
    • Primary fuel filter
  • Generators And Attachments
    • Generator conversion
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, internal excitation, No. of leads = 6, pitch= 0.6667
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, permanent magnet, No. of leads = 6, pitch= 0.6667
    • Space heater
    • 380/400/415volts @ 50 Hz, 3 phase, form wound, permanent magnet, No. of leads = 6, pitch= 0.6667
  • Instrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Manual prelube sump pumps
    • Electric prelube pumps
    • Oil level Reg-1 shallow pan
  • Mounting System
    • IBC vibration isolators
    • Spring-type vibration isolator
  • Protection System
    • Explosion relief valve
  • Special Tests / Reports
    • IBC seismic certifications
    • PGS test report @ 0.8 power factor
    • Neutral grounding connection
    • Neutral ground-LV
    • PGS test report @ 1.0 power factor
  • Starting / Charging Systems
    • Ether starting aid
    • 24 Volt dual electric starting motor
    • 20 Amp battery charger
    • 10 Amp battery chargers
    • Jacket water heaters
    • Oversize battery set
  • General
    • Engine barring group