3516B (50 Hz) with Upgradeable Package

The3516B with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.

Request a Quote
Aspiration
TA
Fuel System
MEUI
Minimum Rating
1750 kVA
Maximum Rating
2500 kVA

Videos not available for this product.

Product Specs

Engine Specifications

Aspiration
TA
Fuel System
MEUI
Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
145 mm (5.71 in)
Stroke
162 mm (6.38 in)
Displacement
32.1 L (1958.86 in3)
Compression Ratio
15.0:1
Governor Type
Adem™A4
Exhaust Flange Size - Internal Diameter
203.2 mm (8.0 in)
Air Inlet
Single element canister style with service indicator
Aspiration
TA
Fuel System
MEUI
Air Inlet
Single element canister style with service indicator
Displacement
1958.9in³
Bore
6.69in
Bore
5.71in
Stroke
6.38in
Stroke
8.46in

Generator Set Specifications

Minimum Rating
1750 kVA
Maximum Rating
2500 kVA
Voltage
220 to 4160 Volts
Frequency
50 Hz
Speed
1500 rpm
Emissions/Fuel Strategy
Low fuel, Low Emissions
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Generator Set Dimensions

Height - Maximum
98.2in
Length - Maximum
247.3in
Width - Maximum
90in
Dry Weight - Genset (maximum)
34250lb

Standard/Optional Features

Standard Equipment:

Optional Equipment:

  • Exhaust System
    • Y-Adapters
  • Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators