DG200-2S (Single-phase)

Electric Power
Electric Power (354)

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
EMCP Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 Listed packages
  • CSA Certified
  • Certain restrictions may apply
  • Consult with your Cat® Dealer
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
EMCP Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 Listed packages
  • CSA Certified
  • Certain restrictions may apply
  • Consult with your Cat® Dealer
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Generator Set Specifications

Voltage
120/240 VAC
Frequency
60 Hz
Natural Gas Rating
200 eKW
Speed
1800 rpm
Emissions/Fuel Strategy
U.S. EPA Certified for Non-Emergency Application
Displacement
864.71in³
Fuel Type
Natural Gas

Engine Specifications

Engine Model
14.2 L Spark - Ignited
Fuel System
Carburetor, Down Draft
Compression Ratio
9.5:1
Governor Type
Electronic
Aspiration
Turbocharged-Aftercooled
Bore
5.31in
Stroke
6.5in

Generator Set Dimensions

Length
127.95in
Width
52.93in
Height
67.37in
Weight
5756lb

Standard/Optional Features

Standard Equipment:

  • Cooling
    • Factory-installed radiator
    • Closed coolant recovery system
    • 50/50 Ethylene glycol antifreeze
    • Standard ambient temperatures up to 50°C (122°F)
    • Radiator and cooling fan complete with protective guards
  • Air Inlet
    • Single element air filter
  • Fuel
    • Fuel pressure test po
    • Primary and secondary fuel shut-off
    • Low fuel pressure switch
    • Dual lock off valves
    • NPT connection
    • Natural Gas or LP Vapor
  • Exhaust
    • Exhaust outlet with 3” pipe
  • Generator
    • Full load capacity alternator
    • Permanent magnet excitation
    • Class H insulation material
    • Integrated Voltage Regulator
    • Matched to the performance and output characteristics of Cat engines
    • IP23 Protection
  • Controls
    • EMCP 4.2 Series generator set controller
  • Mounting
    • Vibration isolaton (puck type)
    • Rubber vibration isolators
  • Electric Starting And/or Prelube
    • Engine electrical system
    • Solenoid activated starter motor
    • Battery cables
  • Electric Power - Package Serial Number Prefix
    • Battery charging alternator
  • Governor
    • Electronic governor (non adjustable)
  • Control Panel
    • EMCP 4.2 Series generator set controller
  • Starting/charging
    • 12 volt starting motor
    • Batteries with rack and cables

Optional Equipment:

  • Starting/charging
    • Battery charger – UL Listed 10 amp
    • Charging alternator
    • Jacket water heater
    • Battery heater
  • General
    • UL 2200 package
    • Enclosures: sound attenuated, weather protective
    • CSA Certification
    • Suitable for Use as Service Equipment (SUSE)
    • Automatic transfer switches (ATS)
  • Generator
    • Shunt trip and auxiliary contact breaker
    • Thermal magnetic or electronic trip MCCBs
    • Anti-condensation heater
    • Excitation: [ ] Permanent Magnet Excited (PM)
    • Anti-condensation heater
    • Oversize and premium generators

Take The Virtual Product Tour To Explore The Features And Benefits of the DG200-2S (Single-phase)

See how DG200 GC (Single-phase) compares against frequently compared products

DG200 GC (Single-phase) Electric Power

Selected Model

Electric Power

View Full Specs

Electric Power

View Full Specs

Compare with other Cat Models

Compare Now

Media Gallery

Check out our current offers

View Specials
Translate »